DKG-307 AUTOMATIC MAINS FAILURE UNIT
The DKG-307 is a comprehensive AMF unit for single genset standby or dual genset mutual standby operations. The unit is available with MPU or CANBUS versions. The CANBUS version connects to ECU controlled electronic engines providing engine control, protection and instrumentation without extra senders.
The unit is able to initiate modem calls and send SMS messages in fault conditions through external modems.
Alternator voltage: 0 to 300 V-AC (Ph-N) |
Alternator frequency: 0-100 Hz. |
Mains voltage: 0 to 300 V-AC (Ph-N) |
Mains frequency: 0-100 Hz. |
DC Supply Range: 9.0 to 33.0 V-DC |
Cranking dropouts: survives 0 V for 100ms. |
Typical Standby Current: 100 mA-DC |
Maximum Operating Current: 250 mA-DC (Relay outputs open) |
Generator/Mains Contactor Relay Outputs: 16 A / 250V |
DC Outputs: 10A @ 28V |
Charge excitation: min 2 Watts |
Magnetic pickup input:: 0.5 - 30 V-AC. |
Magnetic pickup frequency: 10 KHz max. |
Current inputs: from CTs, .../5A. Max load 0.7VA per phase |
Analog input range: 0-5000 ohms. |
Serial port: RS-232, 9600 bauds, no parity, 1 bit stop |
Operating temp.: -40°C (-40°F) to 70°C (158°F). |
Storage temp.: -55°C (-67°F) to 80°C (176°F). |
Maximum humidity: 95% non-condensing. |
Dimensions: 172x 134 x 46 mm (WxHxD) |
Panel Cut-out Dimensions: 151x111 mm minimum. |
Weight: 340 g (approx.) |
Case Material: High Temperature ABS/PC (UL94-V0) |
IP Protection: IP65 from front panel, IP30 from the rear |
Installation: Flat surface mounting on a Type 1 Enclosure. Rear retaining plastic brackets. |