Usage: | Emergency Crew, Standby Unit |
---|---|
Output Type: | AC Three Phase |
Cooling Method: |
Air Cooled |
Still deciding? Get samples of US$ 20/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Leroy Somer AVR R230 regulator for generator
Leroy Somer AVR R230
AVR 230 for generator
Generator regulator R230
R230 regulator for generator
* The alternator with shunt excitation is self-excited with an R230 voltage regulator.
* The regulator monitors the exciter excitation current as a function of the alternator output voltage.
* Very simple in design,the alternator with shunt excitation has no sustaining short-circuit capacity.
* Voltage Regulation:around +/-0.5%
* Voltage supply/sensing range 85 ~139 V (50-60Hz)
* Rapid response time (500 ms) for a transient voltage variation amplitude of ± 20%
* Voltage setting P1
* Stability setting P2.
* Initial potentiometer settings :
1) P1 potentiometer (AVR voltage adjustment): fully anti-clockwise.
2) Remote voltage adjustment potentiometer: centre position.
Run the alternator at its rated speed. If the voltage does not
increase, the magnetic circuit should be remagnetized (see
section 2.3).
3) Turn the AVR voltage adjustment potentiometer P1 slowly
until the output voltage rated value is obtained.
4) Adjust the stability setting using P2.
5) Sealed potentiometer P3 is factory set at 48 Hz for 50 Hz
and 58 Hz for 60 Hz
Technical Data:
Mains input: 0~140VAC 50/60HZ |
Biggest excitation output: DC, 90V/6A/10S |
Examination voltage input: 115VAC |
The lowest residual magnetism gets up urges the voltage:≥5V/25HZ |
Voltage regulation rate:≤±1% |
Outside meets when the voltage trimming 1K/2W potentiometer ±10% |
Operating temperature:-40ºC~70ºC |
Allows to short-circuit the charging current capacity 200% |
Installs the size:130mm X 116mm X 50mm |