ATS106 is an Automatic Transfer Switch Control Module.The module features 32 -Bit microprocessor control.Once mains AC supply failure are detected (under voltage, over voltage), The module will control
generator to start . If generator AC can load, The module automatically transfer the switch to generator AC supply.
Technique Specification
DC supply: 8 to 35V(1.5VA) Single -phase AC input : AC30-277V (+20%) 50/60Hz Relay output: Relay of close mains & close gens 16A 250VAC Relay of start generator 5A 250VAC Delay timers Mains Normal delay time 03 600s Mains Abnormal delay time 03600s Gens Normal delay time 0~3600s Start generator time:0~3600s(after Mains is abnormal) Stop generator time: 0~3600s(after Mains is normal) Close time:0~20.0s Over close time: 0~5.0s Between close time: 0~3600s Mains under voltage: 0~360V Mains over voltage:0~360V Gens under voltage:0~360V Gens over voltage:0~360V Gens under frequency : 0~60.0Hz Gens over frequency : 51.0~75.0Hz Accessorial input:state can be altered by PC Operating Temperature Range: -30 to +70 |
We Offer many brands of Battery Charger, including DeepSea, Mebay, SmartGen, Kipor, etc.