Conditions of Use: |
Marine, Land Use |
---|---|
Usage: | Emergency Crew, Standby Unit, Common Units |
Output Type: | DC |
Still deciding? Get samples of US$ 53/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SPECIFICATION
|
||
DC SUPPLY |
Continuous Votlage Rating
|
8 V to 35 V continuous
|
Maximum Operating Current
|
375 mA at 12 V, 160 mA at 24 V
|
|
Maxinmum Standby Current
|
160 mA at 12 V, 80 mA at 24 V
|
|
Maxinmum Sleep Current
|
35 mA at 12 V, 32mA at 24 V
|
|
Cranking Droputs |
Able to survive 0 V for 50 mS, providing supply was at least
|
|
10 V before dropout and supply recovers to 5 V
|
||
This is achieved without the need for internal batteries
|
||
INPUTS |
Digttal Inputs A to F
|
Negative switching
|
Analogue Inputs D |
Configurable as:
|
|
Negative switching digital input
|
||
0 V to 10 V,4 mA to 20 mA,0 to 240
|
||
Analogue Inputs A TO C |
Configurable as:
|
|
Negative switching digital input:0 to 480
|
||
OUTPUTS |
|
15 A at supply voltage
|
Output B (Start)
|
15 A at supply voltage
|
|
Auxiliary Outputs C, D, E &F
|
2A DC at supply voltage
|
|
GENERATOR & MAINS (UTILITY)
|
Voltage Range
|
15 V to 415 V AC (Ph to N),26 V to 719 V AC (Ph to Ph)
|
Frequency Range
|
3.5 Hz to 75 Hz
|