HAT310 Original SmartGen Controller
Technique Specification
Operating Voltage
|
AC power A1N1/A2N2 supply. Rated AC120V (range: AC90~150V) |
Power Consumption Under rated voltage | power consumption of voltage circuit is not more than 2W |
AC Voltage Input | 3-phase 4-wire (120/208 VAC) |
Gens-set Starter Relay | 16A 120V AC Volts free output (Normally close) |
Mains Close Relay | 16A 120V AC AC Supply output (Normally open) |
Gen Close Relay | 16A 120V AC AC Supply output (Normally open) |
AC Frequency | 50/60Hz |
HAT310 controller can detect 3-phase 4-wire mains voltage/generator single phase voltage and control ATS.
Main characteristics are as follows.
1) With aotomatic charge and automatic recorvery function.
2) With under volatge and loss of phase detection function.
3) LED indicators on the pannal can show working status of controller clearly.
4) Applicable for 2 isolated neutral line.
5) Mains normal delay configured via potentiometer (range: 1~60s), and generator normal delay via
potentiometer (range: 1~60s)
6) Mians is unavailable, if any phase voltage belows minimum working voltage or phase loss occurred
gen-set will be started.
7) Output contact capacity of mains and generator transfer relay is 16A AC250V, which can directly
used to drive switch conversion.
8) Output contact capacity of GENS START relay is 16A AC250V, it is volt free
normally-open/normally-closed contect.
9) Strong anti-electromagnetic interference performance enable controller to use in the enviroment
with strong electromagnetic interfrence.
10) Modular design, self extinguishing ABS plastic shell, pluggable terminal, compact structure;
11) Two installation ways: internal 35mm slideway and internal screw mounting.