Description:
The Marathon SE350 voltage regulator is a critical generator component, ensuring that your generator output voltage is reliable and of high quality. The AVR is a small, but economical, part that controls and regulates the production of voltage by your generator at home or work.
In the majority of applications, the loads fluctuate and are sometimes unpredictable; your AVR is the component charged with ensuring that Marathon alternator is responsive. This means that the alternator is better capable of quickly responding and adapting to load impacts during all operational stages.
The Marathon SE350 is a 100% certified original product exclusively manufactured and engineered by Marathon Electric from the United States. Since 1913, Marathon Electric has produced high quality electric products for various business and residential applications.
This AVR will ensure that you have a constant and stable supply of power in your home or business.
Features and Capabilities:
Sensing & Power Input |
190-240 Vac |
Burden |
500 VA |
Output Power - Continuous |
73 Vdc at 3.5 Adc (255w) |
Output Power - Forcing (240 Vac Input Power) |
105 Vdc at 5 Adc (525w) |
Regulation |
1.0% |
Remote Voltage Adjustment Range |
± 10% with 2000 ohm rheostat ± 5% with l000 ohm rheostat |
Frequency Compensation |
Adjustable |
Roll Off Frequency |
54-61 Hz for 60 Hz 45-51 Hz for 50 Hz |
Operation Weight |
6.5 oz. |
Operating Temperature |
-40°C to +60°C |
Storage Temperature |
-65°C to +85°C |
Power Dissipation |
8 Watts maximum |
Size |
3.94" L X 2.66" W X 2.20: H |
Voltage Buildup |
Internal provisions for automatic voltage build up from generator residual voltage as low as 10 Vac. |
EMI Suppression |
Internal Electromagnetic Interference Filter (EMI Filter) |